Three Phase AC380V 0.75KW High Starting Torque Superior Responsiveness Electric Motor Speed Control Frequency Inverter
Three Phase AC380V 0.75KW High Starting Torque Superior Responsiveness Electric Motor Speed Control Frequency Inverter series frequency Inverter, as a general current vector frequency Inverter with high performance,dedicated to the induction motor drive.Drivers available for packaging, food, fans, pumps and a variety of automated production equipment.
Factory
Specification
Item | Specification | ||
Standard functions | Maximum frequency | Vector contro: 0~300Hz; V/F control: 0~3200Hz | |
Carrier frequency | 0.5kHz~16kHz The carrier frequency is automatically adjusted based on the load features. | ||
Input frequency resolution | Digital setting: 0.01Hz Analog setting: maximum frequency x 0.025% | ||
Control mode | • Sensorless flux vector control (SFVC) • Closed-loop vector control (CLVC) • Voltage/Frequency (V/F) control | ||
Starting torque | • G type: 0.5 Hz/150% (SFVC); 0 Hz/180% (CLVC) • P type: 0.5 Hz/100% | ||
Basic functions | Speed range | 1:100 (SFVC) | 1:1000 (CLVC) |
Constant-speed accuracy | ± 0.5% (SFVC) | ± 0.02% (CLVC) | |
Torque control accuracy. | ± 5% (CLVC) | ||
Overload capacity | • G type: 60s for 150% of the rated current, 3s for 180% of the rated current • P type: 60s for 120% of the rated current, 3s for 150% of the rated current | ||
Torque boost | •Fixed boost • Customized boost 0.1%–30.0% | ||
V/F curve | • Straight-line V/F curve • Multi-point V/F curve •N-power V/F curve (1.2-power, 1.4-power, 1.6-power, ,1.8-power, square) | ||
V/F separation | Two types: complete separation; half separation | ||
Acceleration /deceleration curve | •Straight-line ramp • S-curve ramp Four groups of acceleration/deceleration time with therange of 0.0–6500.0s | ||
DC braking. | DC braking frequency: 0.00Hz~maximum frequency Braking time: 0.0s~36.0s Braking action current value: 0.0%–100.0% | ||
JOG control | JOG frequency range: 0.00–50.00 Hz JOG acceleration/deceleration time: 0.0–6500.0s | ||
Simple PLC and multi-speed operation | It implements up to 16 speeds via the simple PLC function or combination of DI terminal states. | ||
Onboard PID | It realizes process-controlled closed loop control system easily. | ||
Automatic voltage regulation (AVR) | It can keep constant output voltage automatically when the mains voltage changes. | ||
Overvoltage/ Overcurrent stall contro | The current and voltage are limited automatically during the running process so as to avoid frequent tripping due to overvoltage/overcurrent. | ||
Quick current limiting | Maximize overcurrent failure and protect the frequency converter in normal operation | ||
Torque limit and control | It can limit the torque automatically and prevent frequent over current tripping during the running process. Torque control can be implemented in the CLVC mode. | ||
Individualized functions | High performance | Control of asynchronous motor and synchronous motor are implemented through the high-performance current vector control technology. | |
Power dip ride through | The load feedback energy compensates the voltage reduction so that the AC drive can continue to run for a short time. | ||
Rapid current limit | It helps to avoid frequent overcurrent faults of the AC drive. | ||
Timing control | Time range: 0.0–6500.0 minutes | ||
Multi-motor switchover | Four motors can be switched over via four groups of motor parameters. | ||
Bus support | Support field bus: Modbus | ||
Motor overheat protection | The optional I/O extension card enables AI3 to receive the motor temperature sensor input (PT100, PT1000) so as to realize motor overheat protection. | ||
Multiple encoder types | Support difference, open collector and rotary transformer | ||
Operation | Command source | Operation panel, control terminal and serial communication port are given Switch in various methods | |
Frequency source | Various frequency sources: digital reference, analog voltage reference, analog current reference, pulse reference and serial port reference. The switching can be conducted in various methods | ||
Auxiliary frequency source | 10 kinds of auxiliary frequency source. The auxiliary frequency jog and frequency synthesis can be achieved flexibly | ||
Input terminal | Standards: 7 digital input terminals, among which one support maximum high-speed pulse input of 100kHz 2 analog input terminals, among which one only supports voltage input of 0 ~10V and the other supports voltage input of 0 ~10V or current input of 4 ~20mA Expansion capability: 3 digital input terminals 1 analog input terminal, which supports voltage input of -10V ~10V and supports PT100/PT1000 | ||
Operation | Output terminal | Standards: 1 high-speed pulse output terminal (The open collector type is optional), supporting 0~100kHz square signal output 1 digital output terminal 1 relay output terminal 1 analog output terminal, supporting current outpout of 0~20mA or voltage output of 0~10V Expansion capability: 1 digital output terminal 1 relay output terminal 1 analog output terminal, supporting current output of 0~20mA or voltage output of 0~10V | |
Display and keyboard operation | LED display | Display the parameter | |
Key lock and function selection | Realize partial or all key lock and define the action range of some keys to prevent misoperation | ||
Protection function | Short circuit test of electrified motor, input/output default phase protection, overcurrent protection, overvoltage protection, undervoltage protection, overheat protection, overload protection, etc. | ||
Options | IO expansion card, differential input PG card, OC input PG card and rotary transformer PG card. | ||
Environment | Service site | Indoor, free from direct sunshine, no dust, corrosive gas, combustible gas, oil fog, water vapor, drip or salt, etc. | |
Altitude | Less than 1,000m | ||
Ambient temperature | -10℃~ +40℃ (Please use the equipment by derating at ambient temperature of 40℃~50 ℃) | ||
Humidity | Less than 95%RH, no water condensation | ||
Vibration | Less than 5.9m/s2(0.6g) | ||
Storage temperature | -20℃~ +60℃ | ||
IP grade | IP20 | ||
Pollution level | PD2 | ||
Power distribution system | TN , TT |
Wiring mode control loop
The function description of control terminal
Category | Terminal symbol | Terminal name | Function description |
---|---|---|---|
Power supply | +10V-GND | External connection of +10V power supply | Provide power supply of +10V externally, with maximize output current: 10mA It is generally used as working power supply for external potentiometer and the resistance range of potentiometer is 1kΩ~5k Ω |
+24V-COM | External connection of +24V power supply | +24V power supply is provided outwards and generally used as the working power supply for digital input/output terminal and the power supply for external sensor Maximum output current: 200mA | |
OP | Input terminal of external power supply | The factory default is connection to+24V When an external signal is used to drive DI1~DI5, OP shall be connected to external power supply and disconnected from+24V power supply terminal | |
Analog input | AI1-GND | Analog Input Terminal 1 | 1. Input voltage range: DC 0V~10V 2. Input resistance: 22kΩ |
AI2-GND | Analog Input Terminal 2 | 1. Input range: 4mA~20mA, 2. Input resistance: 500Ω for current input. | |
Digital input | DI1- OP | Digital Input 1 | 1. Optical coupler isolation, with bipolar input 2. Input resistance: 2.4kΩ 3. Voltage range in input level: 9V~30V |
DI2- OP | Digital Input 2 | ||
DI3- OP | Digital Input 3 | ||
DI4- OP | Digital Input 4 | ||
DI5- OP | High-speed pulse input terminal | Apart from the characteristics of DI1~DI5, it may be used as high-speed pulse input channel. Maximum input frequency: 50kHz | |
Analog output | AO1-GND | Analog Output 1 | Jumper J5 on the control panel shall determine voltage or current output. Output voltage range: 0V~10V Output current range: 0mA~20mA |
Relay output | T/A-T/C | Open terminal | Contact drive capacity: 25V ac,3A,COSØ=0.4 . 30Vdc ,1A |
Communication interface | 485+,485- | Modbus | Modbus communication interface, non-isolated output |
Daily maintenance
Please make regular inspections to the places which are hard to be inspected during running.
Regular inspection items:
1) Inspect the air channel and clean it regularly
2) Inspect whether the screw is loose
3) Inspect whether the frequency converter suffers from corrosion
4) Inspect whether the terminal block has the arc traces
5) Insulation test for major loop
Remind: when using the megameter (use DC 500V megameter please) to measure the insulation resistance, the major loop line needs to be disconnected with the frequency converter. Do not use the insulation resistance meter to measure the insulation of the control loop. No need to conduct the high voltage test (it is already completed in delivery).